Innovative Solutions in Renewable Energy
LC-C1 adopts modular integrated design
The system includes monitoring, PCS module, LiFePO4 heat sink and fire extinguishing system.It can provide battery, BMS, backup power or emergency power for off-grid important loads.The working mode can also be adjusted to stabilize load fluctuations, peak load shifting, and peak-valley arbitrage.
Advantages
Internal Structure
Solution
Integrated Energy Storage Platform
Benefits from Time-of-Use tariff:AI algorithm, flexibly adapt to the grid and load changes and make energy saving plan based on energy consumption analysis.
Microgrid control:Compatible with the Level 3 BMS.
Supports local Web and cloud access:VPN and/or SCADA control;Remote operation and maintenance.
Production Capacity
Marketing & Service Network
Lenercom's European company is located in Budapest, Hungary. Lenercom Europe provides more convenient and professional localized services for its partners, including warehousing, system maintenance and engineer training.
Cases
As of 2023, we have assisted partners in over 20 countries worldwide by designing customized energy storage solutions for commercial and industrial applications. Our tailored product offerings meet the unique needs of various customers, enabling our partners to effectively address the challenges faced by their end users
Project | Unit | Parameter |
---|---|---|
Model | / | LC-C1-60-129 |
Weight | kg | 1800 |
Size(width/depth/height) | mm | 1424*950*2300 |
Rated Output Power | kW | 60 |
Rated Battery Capacity | kWh | 129 |
Battery Type | / | LiFePO4 |
Cell Rated Capacity | Ah | 120 |
Grid Voltage Range | V | 380×(1±15%)V |
Grid Frequency Range | Hz | 49.5~50.2Hz |
Maximum System Efficiency | % | >86.2% |
Power Factor | / | ±0.99 |
Overload Capacity | / | 110% 10min, 120% 1min |
Conversion Time | ms | <100ms |
Power Command Response Time | ms | <20ms |
AC Voltage THD/Alternating Current THD | % | <5% |
Voltage Unbalance Degree | % | <2% |
Output Phase Deviation | % | <3° |
Off-grid AC Output Voltage | V | 380×(1±2%)V |
Off-grid AC Output Frequency | Hz | 50×(1±0.1%)Hz |
3P4W Output Port (copper bar) | / | 60kW |
PV MPPT Input Port (copper bar) | / | 60kW |
Operation Screen | / | Optional |
Remote Data Monitoring | / | Yes |
Model | LC-C1-50-125 | LC-CI-100-215 |
---|---|---|
Battery Parameters | ||
Battery cell type & capacity | LiFePO4 - 280Ah | LiFePO4 - 280Ah |
Battery storage capacity range | 107.52kWh~125.44kWh | 215kWh |
AC On-Grid Side Parameters | ||
Grid connection type | 3P4W | 3P4W+PE |
Charging / discharging power | 50kW | 100kW |
Rated grid voltage | AC 400V | |
Grid voltage range | ±15% | |
Frequency range | 45Hz ~ 55Hz | |
Rated AC output current | 72A | 144A |
Power factor | 0.8(Leading)~ 0.8(Lagging) | |
Harmonics | ≤5% (rated power) | |
General Parameters | ||
Rated output power [VA] | 1400mm*2100mm*1230mm | 1900mm*2100mm*1330mm |
Maximum weight | About 1660kg | About 2500kg |
Degree of protection | IP55(Battery Cabinet)IP34 (Electrical Cabinet) | |
Cooling method type | Battery Cabinet (air conditioner) & Electrical Cabinet (forced air cooling) | |
Fire fighting system | FM200 automatic fire extinguishing(Novec1230/Aerosol is optional) | FM200 automatic fire extinguishing |
Altitude** | < 2000m, > 2000m The derating is reduced by 5% for every 100m rise | |
Power factor | 0.8 leading to 0.8 lagging | |
Operating temperature* | -20℃~50℃ | |
Noise level | ≤75dB | |
Communication interface | RS485, Ethernet | |
Communication protoco | Modbus RTU, Modbus TCP/IP | |
PV Side Parameters (Optional) | ||
Maximum PV input power | 30kW/60kW/90kW/120kW | 25kW/50kW/100kW |
MPPT voltage range | 200V-850V | |
Maximum input current | 100A/200A/300A/400A | 100A/200A/400A |